General

First tested for lithium-ion fires: the Seefion 16/20 battery safety cabinet

First tested for lithium-ion fires: the Seefion 16/20 battery safety cabinet

The dangers of lithium-ion fires are becoming increasingly well known. Several companies now offer battery storage cabinets. They claim that these cabinets can withstand the force of a battery fire and any resulting explosion. In the absence of specific European regulations and available test results, it is not clear whether all the cabinets on offer are safe.

Safe battery storage is essential. That is why we asked the MPA test institute in Dresden to test the Seefion 16/20 lithium-ion battery safety cabinet. Test result: the fire and explosions remain inside the cabinet! This is an important step towards proven safe storage of lithium-ion batteries. Read on to find out exactly what this means.

Seefion explains:

Risks associated with storing lithium-ion batteries

Lithium-ion batteries must be handled with care. Even the slightest damage can cause a battery to catch fire. The risk increases during charging.

If a battery has been damaged through impact or a manufacturing defect, a chain reaction can occur during charging, causing the battery to catch fire and, in the worst case, even explode. The problem is that damage to a battery cannot be seen from the outside.

How does a lithium-ion battery catch fire?

Lithium-ion batteries are made up of cells. If a cell develops a fault, it can catch fire. The fire then accelerates through a chemical chain reaction, a process known as thermal runaway. The result is an uncontrollable fire in which the battery can explode, with all the consequences that entails.

Test set-up

For this test, a Seefion 16 lithium-ion cabinet was set up in a test room and fitted with temperature and pressure sensors at all critical points. The cabinet was then loaded with 20 fully charged lithium-ion batteries (20 x 400 Wh). 

One of the batteries in the centre of the cabinet was put into thermal runaway, triggering a fault in which a damaged battery spontaneously catches fire.

Test result: little visible from the outside

Although a fierce fire and explosions occurred inside the cabinet, little smoke was visible on the outside. The smoke produced was naturally vented to the outside through the flue.

Result:

  • Fire and explosions remain inside the cabinet.
  • Smoke is vented through the flue.
  • The doors stay closed.
  • No dangerous situation for staff.
  • Sufficient time to alert the fire service.

The test showed that the Seefion cabinet prevents damage and provides valuable time to alert the emergency services. With this test report in hand, Seefion has taken a major step towards proven safe storage of lithium-ion batteries.

Test carried out by MPA Dresden

As there are still no European regulations for the safe storage of lithium-ion batteries, we took the initiative and commissioned a fire test on the Seefion 16/20 lithium-ion battery safety cabinet.

The test protocol was drawn up by the cabinet industry in collaboration with insurers. The renowned MPA Dresden test institute, part of Kiwa, then carried out and documented the test. 

Is the current EN 14470-1 standard not the answer?

Work is currently under way on the PGS 37-2 standard for the safe storage of lithium-ion batteries. This regulation is based on the European EN 14470-1 standard, which was originally intended for the storage of flammable substances.

The current EN 14470-1 standard does not take into account the explosions that can occur during a lithium-ion fire. An EN 14470-1 cabinet protects its contents from an external fire, whereas with lithium-ion batteries the risk is of a fire starting inside the cabinet. Most battery cabinets that comply only with EN 14470-1 are fire-resistant, but have basic door fittings and locks. These fittings and locks cannot withstand a severe lithium-ion fire or the explosions caused by thermal runaway in a lithium-ion battery.

De video laadt pas als je op afspelen klikt.

Question about this story? Ask your question

Companies in this story

Keep following this